DG-P0E.CLO2/MR

DG-P0E.CLO2/MR Digital RS-485 output

Device group: Concentration-measuring gas detectors
Device type: DG-P/MR

Digital DG-P/MR detectors are designed for continuous monitoring of gases indoors. The detector performs cyclic measurements of the gas concentration in ambient air . When preset concentration values are exceeded (for a threshold version), the detector’s optical alarm signaling is activated, the built-in relays change their status and the information is transferred to a digital control module (for the measurement version the concentration value) - using a network in the industrial standard RS-485. The detectors are designed for operation in the Digital Gas Detection System.

The detectors have an exchangeable module with a semiconductor, electrochemical or optical sensor (Infra-Red). The interchangeability of the sensory modules improves maintenance, simplifies calibration and reduces operating costs.

The DG-P/MR detectors are of standard design and cannot be used in areas classified as explosive atmospheres of gases, vapours or dust.

Area of application

  • industrial plants, logistics centres, public facilities;
  • extensive rooms at risk of toxic or explosive gas emissions with locally controlled sirens.

Features

  • communication, control and transmission of information through the port in RS-485 standard, with MODBUS RTU protocol;
  • two alarm thresholds or measurement mode (for electrochemical sensors and Infra-Red);
  • two built-in relays with NO/NC contact, on a removable board (for A1 and A2 state, possibility of threshold adjustment in the measurement mode);
  • sensor in an interchangeable intelligent module (interchangeable with DG/F and DG/P type detectors);
  • sensor can be selected for the application;
  • short detector response time;
  • built-in control microprocessor means reliable and stable operation;
  • thermal compensation system;
  • history of alarm states;
  • semi-automatic addressing in digital network (without opening the housing);
  • removable, screwless terminals with possibility of connecting two FTP wires;
  • selective LED optical optimization;
  • two cable entries – easy connection of successive detectors (loop-through);
  • optionally, the possibility of being equipped with an additional casing made of steel pipes (AR-1d) or a casing for ventilation ducts (DG/w version);
  • configuration of detector settings via dedicated software „DETnet View”, available at https://www.gazex.pl/en/software/;
  • all detectors are calibrated in our own GAZEX Calibration Laboratory operating in accordance with PN-EN ISO/IEC 17025 (PCA accreditation no. AP150).


Device model: DG-P0E.CLO2/MR

Technical parameters

Gas sensor module Sensor Substance/property Standard alarm thresholds or measuring range
MS-P0E.CLO2/N Electrochemical Chlorine dioxide (ClO2)
0 ÷ 1
ppm

Contact control outputs
2
Output in RS-485 standard
Visual signalling, built-in
Supply voltage
24VDC
Dimensions
110 x 140 x 55 mm
Net price
PLN2,399.00 N

Documentation

Series Technical data Device information sheet User Manual Declaration of conformity
W6
W5
W4
W3

Suggested products

Splash-proof enclosures AP-1
Splash-proof enclosures to protect detectors from adverse weather conditions and mechanical damage
Tubular shields AR-1
Profiled tube guards to protect the detector from direct mechanical damage
Gas test sets GTS
Test sets for verifying the correct operation of detectors by injecting a gaseous test mixture into the measuring chamber of the detector